ESTIMATING AIR LEAKAGE

Leakage through the fixed openings should be restricted as much as possible. The amount of expected leakage can be calculated from the following:


Lv = 4005 x (Rp)1/2


L = 4005 x A x (Rp ) 1/2

Where

• Lv = Leakage velocity in FPM

• L = Air leak age in CFM

• Rp = Room pressure in in-WG

• A = Opening area


Assuming 0.05 in-WG room pressures has an opening of 2 sq-ft opening

Leakage velocity = 0.223 x 4005

= 895 feet per minute

With a total of 2 square feet opening size

Leakage air volume = 2 x 895 = 1800 CFM